DVPEN01-SL

Ethernet Communication Module

Operation Manual

DVP-0204320-02

loading

Related Manuals for Delta DVPEN01-SL

Summary of Contents for Delta DVPEN01-SL

  • Page 1
    DVPEN01-SL Ethernet Communication Module Operation Manual DVP-0204320-02…
  • Page 3: Table Of Contents

    LED Indicators…5 RJ-45 PIN Definition…5 INSTALLATION & WIRING …5 Installation …5 CONTROL REGISTER (CR) …6 Control Registers in DVPEN01-SL…6 Explanations on CR …8 Numbering of Left-Side Modules…13 SETTING UP SOFTWARE …14 Setting up Communication & Searching for Modules…14 Basic Settings …20 Network Settings …21…

  • Page 4
    APPLICATION EXAMPLES… 30 Setting up IP and Communicating through WPLSoft… 30 Connecting the PC with DVPEN01-SL through LAN … 33 Setting up Password and Clearing Password … 37 When the Password is Lost (Returning to Default Setting by RS-232)… 39 IP Filter Protection …
  • Page 5: Introduction

    Introduction Thank you for choosing DVPEN01-SL module. To correctly install and operate DVPEN01-SL, please read the manual carefully before using the module. DVPEN01-SL is an Ethernet communication module for remote setting and communication through WPLSoft. DVPEN01-SL is able to send E-mails, automatically correct the RTC in DVP28SV11R/T and exchange data.

  • Page 6: Product Profile & Outline

    Ethernet Communication Module DVPEN01-SL Item Vibration/ Shock Resistance Electrical specifications Item Power supply voltage Power consumption Insulation voltage Weight (g) Product Profile & Outline Dimension Product Profiles 1. Model name 2. Extension port to connect device 3. Extension port to connect I/O module 4.

  • Page 7: Led Indicators

    Fasten the I/O module clip on the left side of the MPU. Connect DVPEN01-SL to other I/O modules To connect DVPEN01-SL with the other I/O module, lift the extension clip of the I/O module by a screwdriver and open the side cover.

  • Page 8: Control Register (Cr)

    Connect DVPEN01-SL to the Network: Connect DVPEN01-SL to the Ethernet Hub by twisted pair cable CAT-5e. DVPEN01-SL has Auto MDI/MDIX function; therefore, DVPEN01-SL does not need to use a crossing cable between the PC and DVPEN01-SL. Network connections between the PC and DVPEN01-SL:…

  • Page 9
    #113 Reserved #114 Modbus TCP time-out DVP-PLC Operation Manual Ethernet Communication Module DVPEN01-SL Content b0 ~ b7: Current status of E-Mail 2 b8 ~ b15: Current status of E-Mail 1 b0 ~ b7: Current status of E-Mail 4 b8 ~ b15: Current status of E-Mail 3 Filled in by the user, and it will be send by E-mail.
  • Page 10: Explanations On Cr

    2. You can read the model code in the program to see if the I/O module exists. CR#1: Firmware Version Explanations: The firmware version of DVPEN01-SL is displayed in hex, e.g. H’0100 indicates version V1.00. CR#2: Communication Mode Explanations: Bit No.

  • Page 11
    When the CR is set as “2”, the data exchange is successful. When the CR is set as “3”, the data exchange fails. DVP-PLC Operation Manual Ethernet Communication Module DVPEN01-SL E-Mail status Not been sent…
  • Page 12
    CR#28: Destination Slave ID Explanations: When you set up the Salve ID (i.e. K1 ~ K255) for data exchange, DVPEN01-SL will automatically search for the corresponding IP address from the Slave IP list. For example, if the ID is set as “0”, the value in CR#25 and #26 will be regarded as the destination IP.
  • Page 13
    D8 ~ D11 of the Master will be written into D2 ~ D5 of the Slave. Both sending and receiving can be executed at the same time. When the values in CR#82 and #85 are both “0”, DVPEN01-SL will use the default registers (CR#29 ~ CR#68) and number of registers (K20).
  • Page 14
    Ethernet Communication Module DVPEN01-SL CR#114: Modbus TCP Time-Out Explanations: Setting up the communication time-out (in ms) for Modbus TCP mode. CR#115: Modbus TCP Trigger Explanations: When the CR value is set as “1”, Modbus TCP will be triggered. After the data transmission is completed in Modbus TCP mode, the CR value will automatically be reset to “0”.
  • Page 15: Numbering Of Left-Side Modules

    Status of RTU slave 4 Numbering of Left-Side Modules After DVPEN01-SL is installed properly, you need to compile the PLC program to control the special I/O module. PLC offers FROM instruction (for reading) and TO instruction (for writing) to control the control registers (CR) in the special I/O module.

  • Page 16: Setting Up Software

    Before you start a setup page, you have to select “Ethernet” in the communication setting. Next, you can search by IP address or use Auto-Search. You also can open the setup page for DVPEN01-SL by RS-232. DVPEN01-SL is set up by UDP port 20006; therefore, you have to be aware of the relevant settings of the firewall.

  • Page 17
    Broadcast search 1. Click broadcast icon in DCISoft to search for all Delta Ethernet products on the network. The window on the left hand side shows the models found, and the window on the right hand side displays the device list of all models.
  • Page 18
    Ethernet Communication Module DVPEN01-SL 3. You will see the basic setup page as follow. Designating model to search 1. Right click “Ethernet” on the left hand side window and select “Configure” to designate a model to search for. DVP-PLC Operation Manual…
  • Page 19
    Ethernet Communication Module DVPEN01-SL 2. After configure a model, select “DVPEN01-SL” and click “OK” to auto-search for DVPEN01-SL modules on the network. 3. List of the current DVPEN01-SL modules DVP-PLC Operation Manual…
  • Page 20
    1. Set the communication type to “Ethernet” and enter the IP address. Click “OK”. 2. Click “IP Search” icon to start searching for the designated IP. 3. The DVPEN01-SL module found will be displayed in the right hand side window. Double click it to enter the setup page.
  • Page 21
    1. Select “RS232″ as the transmission type in communication setting. You will have to designate a communication port. When DVPEN01-SL is searched by RS-232, you do not need to set up the parameters (i.e. data length, parity, stop bits and baud rate).
  • Page 22: Basic Settings

    Setting up DVPEN01-SL basics 1. Module Name: There can be many DVPEN01-SL modules in the network. Thus, you can set up a module name for each module to identify the module when you need to use them. 2. Module Language: You can select a language for each module name, and the windows will be displayed in the selected language.

  • Page 23: Network Settings

    Setting up static IP of the PC 1. Enter Control Panel → Network Connection → click on “Local Area Connection” 2. You will see the “Local Area Connection Status” window. Click on “Properties”. DVP-PLC Operation Manual Ethernet Communication Module DVPEN01-SL…

  • Page 24
    Ethernet Communication Module DVPEN01-SL 3. Click on “Internet Protocol (TCP/IP). 4. Enter 192.168.0.1 into IP address. Click on “OK” to complete the IP address setting of the PC. DVP-PLC Operation Manual…
  • Page 25
    For example, if the LAN has to be connected to WAN, it will need a gateway to bridge the communication. The IP of the gateway has to be in the same subnet as DVPEN01-SL. The default gateway IP address of DVPEN01-SL is 192.168.1.1.
  • Page 26: Setting Up E-Mails

    DVPEN01-SL offers 4 sets of E-Mail information, and you can self-define the register or bit information to be read. When the trigger occurs, DVPEN01-SL will add the set register or bit present value read to the E-Mail. Every set of E-Mail information is able to contain maximum 100 continuous register data.

  • Page 27: Data Exchange

    3. Communication Address & Data exchange host IP: You have to enter the IP address of DVPEN01-SL at the other end. For example, if you would like DVPEN01-SL to exchange data with 192.168.0.1, set No. 1 as 192.168.0.1. When the data are being exchanged, if the value in CR#28 is H’0001, the data will be exchanged with…

  • Page 28: Rtu

    Use the “RTU” function to conduct mapping between Delta’s network modules DVPEN01-SL and RTU-EN01.Set up the mapping information first, and you will be able to use WPLSoft in DVPEN01-SL to save and retrieve the mapped bit (M) and register (D) in order to operate the remote RTU-EN01.

  • Page 29: Ip Filter

    MAC address. You can use ARP to look up the MAC address by IP address, and the corresponding MAC address will be saved, so you do not need to look it up again when sending the next datum. DVP-PLC Operation Manual Ethernet Communication Module DVPEN01-SL…

  • Page 30: Setting Up Password

    Incorrect settings may result in connection failure. Therefore, DO NOT set the MAC address of the equipment without the network into the table. Setting up Password To prevent the set values in DVPEN01-SL from being modified, you can set up password to lock the settings in DVPEN01-SL. Setting up DVPEN01-SL password…

  • Page 31: 5.10 Returning To Default Setting

    After the password is locked, all the pages cannot be set up unless you unlock the password. However, if you set up DVPEN01-SL by RS-232, you can return the setting to default setting whether the password is locked or not. For example, if you have locked DVPEN01-SL but forget the password, you have to return DVPEN01-SL to factory default setting by RS-232, and all the settings will return to default ones.

  • Page 32: Application Examples

    Check “Default Setting” box and click on “Yes”. Note: If you set up DVPEN01-SL by RS-232, you can return the setting to default setting whether the password is locked or not. It takes approximately 10 seconds to return to default setting, so DO NOT switch off the power within the 10 seconds.

  • Page 33
    Ethernet Communication Module DVPEN01-SL 3. Select “Ethernet” and press «OK”. 4. Click on “Auto-Search” icon to search for all DVPEN01-SL modules in the network. 5. Designate a DVPEN01-SL and double click it to open the setup page. DVP-PLC Operation Manual…
  • Page 34
    Ethernet Communication Module DVPEN01-SL 6. Open “Basic” setup page. 7. Switch to “Network” setup page DVP-PLC Operation Manual…
  • Page 35: Connecting The Pc With Dvpen01-Sl Through Lan

    WPLSoft will automatically search for DVPEN01-SL. 9. The IP of DVPEN01-SL has been modified into the new setting (DELTA DVPEN01-SL: 192.168.0.4). 10. Click on DELTA DVPEN01-SL, and WPLSoft will be able to communicate with the MPU. Connecting the PC with DVPEN01-SL through LAN Application Setting up network parameters of DVPEN01-SL by WPLSoft through LAN.

  • Page 36
    Ethernet Communication Module DVPEN01-SL 2. Open “Communication Setting” in WPLSoft. 3. Select “Ethernet” and press “OK”. DHCP Server DVPEN01 DVP-PLC Operation Manual DVP-PLC…
  • Page 37
    4. Click on “Auto-Search” icon to search for all DVPEN01-SL modules in the network. Follow “View Workspace Communication” or “View DVPEN01-SL module (default module name: DELTA DVPEN01-SL, IP: 192.168.1.5) in the window. 5. Designate a DVPEN01-SL and double click it to open the setup page.
  • Page 38
    6. Open the setup page. You can modify the module name for easier identification. 7. Next, set up the new IP of DVPEN01-SL. First switch to “Network” setup page. If there is a DHCP server in the LAN, select DHCP in “IP Configuration”. If there is no DHCP server in the LAN, you can set a static IP.
  • Page 39: Setting Up Password And Clearing Password

    3. Check “Modify” box and enter “aabb” in “New Password” and “Confirm Password» columns. Click on “OK” to save the password. 4. Open the setup page again, and DVPEN01-SL is now locked by the password. You cannot open any of the settings now. Click on “Unlock” to leave the entering password window.

  • Page 40
    Ethernet Communication Module DVPEN01-SL 5. Enter the password to temporarily unlock the protection and modify the parameters. If you close the setup page, the locking will automatically be recovered. 6. To clear the password, simply leave the password columns blank. Click on “OK” to clear the password.
  • Page 41: When The Password Is Lost (Returning To Default Setting By Rs-232)

    (1) DVPEN01-SL is set with a password. requirement (2) The password is forgotten. 1. Use DVPACAB2A30 cable to connect the PC and DVPEN01-SL and open the setup page. Open the “reset to default setting”” pages. Click on “Unlock”. DVP-PLC Operation Manual…

  • Page 42: Ip Filter Protection

    IP Filter Protection Application Setting up IP filter protection Network (1) IP of DVPEN01-SL: 192.168.0.4 requirement (2) Only connections to 192.168.0.7 and 172.16.0.1~172.16.0.255 are allowed. 1. See 6.1 for the connection and how to set up the communication. 2. Open the setup page and switch to “IP Filter” page.

  • Page 43
    3. Check “Enable IP Filter Function” box. Enter “192.168.0.4” in No. 1 IP and “255.255.255.255” in all “Netmask” columns. 4. Enter “192.168.0.1” in No. 2 IP and “255.255.255.0” in No.2 “Netmask” column. Click on «OK” to complete the setting. Only the equipment within the IP range can be connected. DVP-PLC Operation Manual Ethernet Communication Module DVPEN01-SL…
  • Page 44: Setting Up Static Arp Table

    1. See 6.1 for the connection and how to set up the communication. 2. Open the setup page and switch to “Static ARP Table” page. 3. Check “Enable ARP Table” box. Enter “192.168.1.6” in No. 1 IP, and its corresponding MAC address is “00:18:23:10:00:35”.

  • Page 45
    Only the equipment within the IP range can be connected. Note: The MAC address of DVPEN01-SL can be obtained from WPLSoft or the MAC address sticker on the equipment. The MAC address of PC can be found in the “Network Connection Details” (see below).
  • Page 46: Application Of E-Mail

    Ethernet Communication Module DVPEN01-SL Application of E-Mail Sending an E-Mail to notify the administrator when the current status of X0 and Y0 is Application changed. Network (1) SMTP Server IP: 172.16.144.121。 application (2) E-mail address of administrator: test@sample.com (3) An E-mail message will be generated when the status of X0 and Y0 is changed.

  • Page 47: Application Of Data Exchange (1)

    4. Switch to “Select Recipients” page. Check all the boxes of “Recipient 1”. Click on “OK” to complete the setting. 5. After all the settings in DVPEN01-SL are completed, compile the ladder diagram in the MPU and download it to the MPU. See below for the program design: Explanations: •…

  • Page 48
    Ethernet Communication Module DVPEN01-SL 1. See 6.1 for how to set up the communication. 2. Open the setup page of PLC_B and switch to “Data Exchange” page. 3. Check “Enable Data Exchange” box. Select “Program Control” for Execute Mode. Enter IP address of PLC_A “192.168.0.4”…
  • Page 49
    • The data exchange will be executed every one second. • Write the communication address of the destination PLC in CR#28, and DVPEN01-SL will automatically detect by the previous setting that No. 1 IP is “192.168.0.4″. • Write the data in RTC into CR#29 ~ CR#35.
  • Page 50: Application Of Data Exchange (2)

    (4) Update from PLC_A to PLC_B and PLC_B to PLC_A. 1. See 6.1 for how to set up the communication. 2. Open the setup page of PLC_A and switch to “Data Exchange” page. Check “Enable Data Exchange” box. Select “Always Enable” for Execute Mode. Enter IP address of PLC_B “192.168.1.97”, D200 D0 Quantity: 100 and D0 D0 Quantity: 100 in No.

  • Page 51: Application Of Data Exchange (3)

    (4) Update from PLC_A to PLC_B and PLC_B to PLC_A. 1. See 6.1 for how to set up the communication. 2. Open the setup page of PLC_A and switch to “Data Exchange” page. 3. Check “Enable Data Exchange” box. Select “Program Control” for Execute Mode. Enter IP address of PLC_B “192.168.1.97”, D200 D0 Quantity: 100 and D0 D0 Quantity: 100 in No.

  • Page 52: Application Of Data Exchange (4)

    Ethernet Communication Module DVPEN01-SL After all the settings in PLC_A are completed, compile the ladder diagram in the MPU and download it to PLC_A. See below for the program design: 6.11 Application of Data Exchange (4) Writing the time in RTC in PLC_B into D0 ~ D6 of PLC_A by designating IP by ladder Application diagram.

  • Page 53
    2. Compile the ladder diagram for PLC_A and download it to PLC_A. M1013 Explanations: • The received data are stored in CR#49 ~ CR#55. • The data received every one second are written into D0 ~ D6. DVP-PLC Operation Manual Ethernet Communication Module DVPEN01-SL D100 K100 K100 HC0A8 K100 K100 D100…
  • Page 54: Application Of Data Exchange (5)

    Ethernet Communication Module DVPEN01-SL 6.12 Application of Data Exchange (5) Writing the time in RTC in PLC_B directly into D0 ~ D6 of PLC_A without writing in ladder Application diagram into PLC_A. Network (1) Adopting static IP. requirement (2) IP of PLC_A: 192.168.0.4 (3) IP of PLC_B: 192.168.0.5…

  • Page 55: 6.13 Application Of Modbus Tcp Master

    2. Compile the ladder diagram in the MPU and download it to PLC_B. See below for the program design. We do not need to write any corresponding ladder diagram into PLC_A. M1013 = D0 K0 = D0 K1 DVP-PLC Operation Manual Ethernet Communication Module DVPEN01-SL K100 K118 HC0A8 K100 K117…

  • Page 56: 6.14 Rtu Mapping

    (5) Set up the mapping start address and number of data for RX, RY, RCR (read) and RCR (write) at DVPEN01-SL. (6) Enable the mapping function in DVP-SV PLC at DVPEN01-SL. Use M2000 and D2000 in DVP-SV to read and M3000 and D3000 to write the value in the remote RTU-EN01.

  • Page 57
    2. Use DCISoft for RTU-EN01 to set up the mapping CR for read/write. 3. Use DCISoft for DVPEN01-SL to set up the mapping start address and number of data. RX: M2000 ~ M2009, RY: M3000 ~ M3009, RCR Read: D2000 ~ D20009, RCR Write: D3000 ~ D3009 4.
  • Page 58
    Ethernet Communication Module DVPEN01-SL Explanations: 1. Enable mapping: CR15 = 1 2. Disable mapping: CR15 = 0 3. Once CR#15 is enabled, M2000 ~M2009 and D2000 ~ D2009 will read the data, and M3000 ~ M3009 and D3000 ~ D3009 will read the present value before starting to write.

Скачать

Страница из 58

DVPEN01-SL   

Ethernet Communication Module 

 
Operation Manual 

DVP-0204320-02 

Loading…

DVPEN01-SL

Ethernet Communication Module

Application Manual

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

1

Warning

3

Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent

damages on the device or injuries to staff.

3

Switch off the power before wiring.

3

RTU-DNET is an OPEN TYPE device and therefore should be installed in an enclosure free of airborne dust,

humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the

device (e.g. key or specific tools are required for operating the enclosure) in case danger and damage on the

device may occur.

3

RTU-DNET is to be used for controlling the operating machine and equipment. In order not to damage it, only

qualified professional staff familiar with the structure and operation of RTU-DNET can install, operate, wire and

maintain it.

3

DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check

all the wirings again before switching on the power and DO NOT touch any terminal when the power is switched

on. Make sure the ground terminal

is correctly grounded in order to prevent electromagnetic interference.

Table of Contents

1 INTRODUCTION…………………………………………………………………………………………………………………..3

1.1 Functions…………………………………………………………………………………………………………………….3

1.2 Specifications …………………………………………………………………………………………………..………….3

2 PRODUCT PROFILE & OUTLINE ………………………………………………………………………………………….4

2.1 Dimension …………………………………………………………………………………………………………………..4

2.2 Product Profiles……………………………………………………………………………………………………………4

2.3 LED Indicators……………………………………………………………………………………………………………..5

2.4 RJ-45 PIN Definition……………………………………………………………………………………………………..5

3 INSTALLATION & WIRING …………………………………………………………………………………………….……..5

3.1 Installation …………………………………………………………………………………………………….…………….5

4 CONTROL REGISTER (CR) …………………………………………………………………………………………….……6

4.1 Control Registers in DVPEN01-SL…………………………………………………………………………………. 6

4.2 Explanations on CR ……………………………………………………………………………………………………..8

4.3 Numbering of Left-Side Extension Modules……………………………………………………………………12

5 SETTING UP SOFTWARE…………………………………………………………………………………………………..13

5.1 Setting up Communication & Searching for Modules……………………………………………………….13

5.2 Basic Settings …………………………………………………………………………………………………..……….16

5.3 Network Settings ………………………………………………………………………………………………………..18

5.4 Setting up E-Mails ……………………………………………………………………………………………….……..20

5.5 Data Exchange…………………………………………………………………………………………………………..22

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

2

5.6 IP Filter ……………………………………………………………………………………………………………………. 23

5.7 Static ARP Table ……………………………………………………………………………………………………….. 24

5.8 Setting up Password………………………………………………………………………………………………….. 25

5.9 Returning to Default Setting ……………………………………………………………………………………….. 26

5.10 Export & Import of DVPEN01-SL Files …………………………………………………………………………. 27

5.11 Recording IP Address ……………………………………………………………………………………………..…. 28

6 APPLICATION EXAMPLES……………………………………………………………………………………………..…. 29

6.1 Setting up IP and Communicating through WPLSoft………………………………………………………. 29

6.2 Connecting the PC with DVPEN01-SL through LAN………………………………………………………. 32

6.3 Setting up IP and Communicating through WPLSoft………………………………………………………. 36

6.4 Setting up Password and Clearing Password ……………………………………………………………….. 37

6.5 When the Password is Lost (Returning to Default Setting by RS-232)………………………………. 39

6.6 IP Filter Protection ……………………………………………………………………………………………..……… 40

6.7 Setting up Static ARP Table………………………………………………………………………………………... 42

6.8 Application of E-Mail…………………………………………………………………………………………….……. 43

6.9 Application of Data Exchange (1) ………………………………………………………………………………… 45

6.10 Application of Data Exchange (2) ………………………………………………………………………………… 47

6.11 Application of Data Exchange (3) ………………………………………………………………………………… 48

6.12 Application of Modbus TCP Master (1)…………………………………………………………………………. 49

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

3

1 Introduction

Thank you for choosing DVPEN01-SL module. To correctly install and operate DVPEN01-SL, please read

the manual carefully before using the module.

DVPEN01-SL is an Ethernet communication module for remote setting and communication through

WPLSoft. DVPEN01-SL is able to send E-mails, automatically correct the RTC in DVP28SV11R/T and

exchange data. It supports Modbus TCP communication protocol and can conduct remote monitoring by using

SCADA (Supervisor Control And Data Acqusition) software or HMI (Human Machine Interfaces). DVPEN01-SL

can be the master of Modbus TCP, sending out Modbus TCP instrcutions and controlling the peripheral

equipment. In addition, under MDI/MDI-X auto-detection, it does not need to use a crossing cable. See the

contents below for more detailed instructions on DVPEN01-SL module.

1.1 Functions

z Auto-detects 10/100Mbps transmission speed

z MDI/MDI-X auto-detection

z Supports Modbus TCP protocol (at the same time supports Master and Slave mode)

z Able to send out E-mails

z Auto-corrects the RTC in PLC through the Internet time correction function

z Supports point-to-point data exchange (Max. data exchange length: 200 bytes)

1.2 Specifications

Internet interface

Item Specification

Interface RJ-45 with Auto MDI/MDIX

Number of ports 1 Port

Transmission method IEEE802.3, IEEE802.3u

Transmission cable Category 5e

Transmission speed 10/100 Mbps Auto-Detect

Network protocol ICMP, IP, TCP, UDP, DHCP, SMTP, NTP, Modbus TCP

Serial communication interface

Item Specification

Interface RS-232

Number of ports 1 Port

Transmission cable DVPACAB230, DVPACAB215, DVPACAB2A30, DVPACAB2B10

Environment

Item Specification

Noise immunity

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge

EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV

Analog & Communication I/O: 1KV

Damped-Oscillatory Wave: Power Line: 1KV

RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

Environment

Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree 2;

Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

4

Item Specification

Vibration/ Shock Resistance Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

Electrical specifications

Item Specification

Power supply voltage 24VDC (-15% ~ 20%) (Power is supplied by the internal bus of MPU.)

Power consumption 1.5W

Insulation voltage 500V

Weight (g) 92 (g)

2 Product Profile & Outline

2.1 Dimension

LAN

RS-232

LINK

DVPEN01

RS-232

POWER

100M

60 [2.362]

90 [3.543]

3 [0.118]

Unitmm [inches]

2.2 Product Profiles

LAN

RS-232

LINK

DVPEN01

RS-232

POWER

100M

1

4

3

7

5

6

9

8

2

1. Model name 6. Fixing tenon for extension unit/module

2. Extension port to connect device 7. Fixing clip for extension unit/module

3. Extension port to connect extension module 8. RS-232 connection port

4. POWER, LINK, RS-232, 100M indicators 9. Ethernet RJ-485 connection port

5. DIN rail clip

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

5

2.3 LED Indicators

Indicator Color Indication

POWER Green Power indication

RS-232 Red Communication status of the series port

100M Orange Network connection status

LINK Green Network communication speed

2.4 RJ-45 PIN Definition

RJ-45 sketch Terminal No. Definition Explanation

1 Tx+ Positive pole for data transmission

2 Tx- Negative pole for data transmission

3 Rx+ Positive pole for data receiving

6 Rx- Negative pole for data receiving

4, 5, 7, 8 N/C

3 Installation & Wiring

This section gives instructions on how to connect DVPEN01-SL with PLC MPU and how to connect

DVPEN01-SL to the network.

3.1 Installation

Connect PLC MPU to DVPEN01-SL

z Adjust the extension clip on the left side of the MPU.

z Meet the extension port of the MPU with DVPEN01-SL as shown in the figure below.

z Fasten the extension clip.

DVP28SV

LAN

RS-232

RS-232

LINK

100M

DVPEN01

POWER

Connect DVPEN01-SL to other extension modules

z To connect DVPEN01-SL with the other extension module, lift the extension clip of the extension

module by a screwdriver and open the side cover.

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

6

Connect DVPEN01-SL to the Network

Connect DVPEN01-SL to the Ethernet Hub by twisted pair cable CAT-5e. DVPEN01-SL has Auto MDI/MDIX

function; therefore, DVPEN01-SL does not need to use a crossing cable between the PC and DVPEN01-SL.

Network connection between the PC and DVPEN01-SL:

4 Control Register (CR)

4.1 Control Registers in DVPEN01-SL

CR#

HW LW

Attribute Content Explanation

#0 R Model name

Set up by the system; read only. Model code of DVPEN01-SL

= H’4050

#1 R Firmware version Displaying the current firmware version in hex.

#2 R Communication mode b0: Modbus TCP mode; b1: data exchange mode

#3 W E-Mail Event 1 trigger Set up whether to send E-Mail 1

#4 W E-Mail Event 2 trigger Set up whether to send E-Mail 2

#5 W E-Mail Event 3 trigger Set up whether to send E-Mail 3

#6 W E-Mail Event 4 trigger Set up whether to send E-Mail 4

Ethernet

PC Maste

DVP28SV

LAN

RS-232

RS-232

LINK

100M

DVPEN01

POWER

DVP28SV

DVPEN01

DVP28SV

LAN

RS-232

RS-232

LINK

100M

DVPEN01

POWER

DVP28SV

DVPEN01

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

7

CR#

HW LW

Attribute Content Explanation

#7 R

Status of E-Mail 1, 2 b0 ~ b7: Current status of E-Mail 2

b8 ~ b15: Current status of E-Mail 1

#8 R Status of E-Mail 3, 4

b0 ~ b7: Current status of E-Mail 4

b8 ~ b15: Current status of E-Mail 3

#9 R/W

E-Mail 1 additional

message

Filled in by the user, and it will be send by E-mail.

#10 R/W

E-Mail 2 additional

message

Filled in by the user, and it will be send by E-mail.

#11 R/W

E-Mail 3 additional

message

Filled in by the user, and it will be send by E-mail.

#12 R/W

E-Mail 4 additional

message

Filled in by the user, and it will be send by E-mail.

#13 R/W Data exchange trigger Set up whether to send out data in data exchange mode

#14 R Status of data exchange Displaying current status of data exchange.

#24 ~ #15 Reserved

#26 #25 R/W Destination IP Destination IP address for data exchange

#27 Reserved

#28 R/W Destination Slave ID Destination Slave ID for data exchange

#48 ~ #29 R/W Data transmission buffer Buffer for transmitted data in data exchange

#68 ~ #49 R Data receiving buffer Buffer for received data in data exchange

#69 R/W DHCP/Static IP Selecting DHCP or Static IP

#71 #70 R/W IP address Setting up IP address

#73 #72 R/W Subnet mask Setting up subnet mask of DVPEN01-SL

#75 #74 R/W Gateway Setting up default gateway IP address

#76 R IP status Displaying current IP status

#80 ~ #77 Reserved

#81 R/W

Read address for data

exchange

Slave transmission buffer address for data exchange

#82 R/W

Read length for data

exchange

Number of registers for read data

#83 R/W

Received address for

data exchange

Buffer address for the receiving Master in data exchange

#84 R/W

Written-in address for

data exchange

Buffer address for the receiving Slave in data exchange

#85 R/W

Written-in length for data

exchange

Number of registers for data transmission

#86 R/W

Transmission address

for data exchange

Master transmission buffer address for data exchange

#110 ~ #87 Reserved

#111 R/W 8-bit processing mode Setting up Modbus TCP Master control as 8-bit mode

#113 ~ #112 Reserved

#114 R/W Modbus TCP time-out Setting up Modbus TCP time-out (in ms)

#115 R/W Modbus TCP trigger Setting up whether to send out data in Modbus TCP mode

#116 R/W Modbus TCP status Displaying current status of Modbus TCP mode

#118 #117 R/W

Modbus TCP

destination IP

Setting up destination IP address for Modbus TCP transaction

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

8

CR#

HW LW

Attribute Content Explanation

#119 R/W Modbus TCP data length Setting up the data length for Modbus TCP transaction

#219 ~ #120 R/W Modbus TCP data buffer Data buffer of Modbus TCP for storing sending/receiving data

#248 ~ #220 Reserved

#251 R Error code

Displaying the errors. See table of error codes in the following

section for more information.

#255 ~ #252 Reserved

Symbols “R” refers to “able to read data by FROM instrcution”; “W” refers to “able to write data by TO

instrcution”.

4.2 Explanations on CR

CR#0: Model Name

Explanations:

1. Model code of DVPEN01-SL = H’4050.

2. You can read the model code in the program to see if the extension module exists.

CR#1: Firmware Version

Explanations:

The firmware version of DVPEN01-SL is displayed in hex, e.g. H’0100 indicates version V1.00.

CR#2: Communication Mode

Explanations:

Bit No. Mode “0” “1”

b0 Modbus TCP Disable Enable

b1 Data exchange Disable Enable

E-mail Functions

CR#3 ~ 6: E-Mail Event 1 ~ 4 Trigger

Explanations:

When the CR is set as “1”, E-mail sending will be enabled. After the sending is completed, the

CR will automatically be reset as “0”. Note: Please trigger by differential instrcutions.

CR#7 ~ 8: Status of E-Mail 1 ~ 4

Explanations:

1. CR#7_b0 ~ b7: current status of E-Mail 2; CR#7_b8 ~ b15: current status of E-Mail 1.

2. CR#8_b0 ~ b7: current status of E-Mail 4; CR#8_b8 ~ b15: current status of E-Mail 3.

3. Table of E-Mail status

CR value E-Mail status

0 Not been sent

1 Being processed

2 E-Mail sending is successful

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

9

CR value E-Mail status

10 Fail to connect to SMTP-Server

11 Incorrect recipient E-Mail address

12 SMTP-Server communication error

13 Exceeding the max. number of TCP connection

3 ~ 9, 14 ~ 255 Reserved

CR#9 ~ 12: E-Mail 1 ~ 4 Additional Message

Explanations:

The user fills in the code, and the code will be stored in the title of the E-Mail and sent out with the

E-Mail.

Data Exchange

CR#13: Data Exchange Trigger

Explanations:

When the CR is set as “0”, the data in data exchange area will not be transmitted. When the CR is

set as “1”, the data in data exchange area will be transmitted.

CR#14: Data Exchange Status

Explanations:

When the CR is set as “0”, the data have not yet been received. When the CR is set as “1”, the

data exchange is in progress. When the CR is set as “2”, the data exchange is successful. When

the CR is set as “3”, the data exchange fails.

CR value Status

0 Data have not yet been received.

1 Data exchange is in progress.

2 Data exchange is successful.

3 Data exchange fails.

CR#25, 26: Destination IP

Explanations:

To set up the Slave IP address for data exchange manually, write “0” into CR#28 first before

setting up the destination IP. See explanations on CR#70 and #71 for how to set.

CR#28: Destination Slave ID

Explanations:

When you set up the Salve ID (i.e. K1 ~ K255) for data exchange, DVPEN01-SL will

automatically search for the corresponding IP address from the Slave IP list. For example, if the

ID is set as “0”, the value in CR#25 and #26 will be regarded as the destination IP.

CR#29 ~ 48: Data Transmission Buffer

Explanations:

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

10

Storing the data to be transmitted to the remote MPU.

CR#49 ~ 68: Data Receiving Buffer

Explanations:

Storing the data received from the remote MPU.

CR#81: Read Address for Data Exchange

Explanations:

Setting up manually the Modbus address of the register for Slave data exchange. Only register

address is allowed (e.g. D0 = H’1000).

CR#82: Read Length for Data Exchange

Explanations:

The number of receiving registers (K1 ~ K128) in data exchange.

CR#83: Read Length for Data Exchange

Explanations:

Setting up the Modbus address of the register for Master data exchange.

CR#84: Written-in Address for Data Exchange

Explanations:

Setting up manually the Modbus address of the register for Slave data exchange.

CR#85: Written-in Address for Data Exchange

Explanations:

The number of transmission registers (K1 ~ K128) in data exchange.

CR#86: Transmission Address for Data Exchange

Explanations:

1. Setting up the Modbus address of the register for Master data exchange.

2. Example: Write H’1000 (D0) into CR#81, K1 into CR#82, and H’1064 (D100) into CR#83. If

the data exchange is successful, the value in D0 of the Slave will be written into D100 of the

MPU. Or write H’1002 (D2) into CR#84, K4 into CR#85, and H’1008 (D8) into CR#86. If the

data exchange is successful, the value in D8 ~ D11 of the Master will be written into D2 ~ D5

of the Slave. Both sending and receiving can be executed at the same time. When the values

in CR#82 and #85 are both “0”, DVPEN01-SL will use the default registers (CR#29 ~ CR#68)

and number of registers (K20).

Network Settings

CR#69: DHCP/Static IP

Explanations:

You can select either DHCP or Static IP. When the CR value is set as “0” Æ Static IP; When the

CR value is set as “1” Æ DHCP (dynamic IP).

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

11

CR#70, 71: IP Address

Explanations:

1. Setting up the IP address of our equipment in hex. When in DHCP mode, you can only read

and cannot write.

2. Example: Assume you’d like to set the IP address as 192.168.0.2, you have to write H’0002

into CR#70 and H’C0A8 into CR#71 to complete the setting. (K192 = H’C0, K168 = H’A8, K0

= H’00, K2 = H’02

CR#72, 73: Subnet Mask

Explanations:

1. Setting up the subnet mask of our equipment in hex. When in DHCP mode, you can only read

and cannot write.

2. Example: Assume you’d like to set the subnet mask as 255.255.255.0, you have to write

H’FF00 into CR#72 and H’FFFF into CR#73 to complete the setting.

CR#74, 75: Gateway

Explanations:

Setting up the gateway of our equipment in hex. When in DHCP mode, you can only read and

cannot write. See the explanations on CR#70 and #71 for how to set.

CR#76: IP Status

Explanations:

Displaying the current IP status. When the CR value is “0” Æ normal status; when the CR value

is “1” Æ DHCP setting has not completed; when the CR value is “2” Æ IP setting in progress.

Sending Modbus TCP Instruction

CR#111: 8-bit Processing Mode

Explanations:

Setting up the Modbus TCP transmission mode. When the CR value is set as “0” Æ 16-bit mode;

when the CR value is set as “1” Æ 8-bit mode.

CR#114: Modbus TCP Time-Out

Explanations:

Setting up the communication time-out (in ms) for Modbus TCP mode.

CR#115: Modbus TCP Trigger

Explanations:

When the CR value is set as “1”, Modbus TCP will be triggered. After the data transmission is

completed in Modbus TCP mode, the CR value will automatically be reset to “0”. Please trigger

by differential instructions.

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

12

CR#116: Modbus TCP Status

Explanations:

Displaying the current communication status of Modbus TCP mode. When the CR value is set

as”0” Æ the data have not yet been received; when the CR value is set as “1” Æ the data

exchange is in progress; when the CR value is set as “2” Æ the data exchange is successful;

when the CR value is set as “3” Æ the data exchange fails.

CR value Data exchange status

0 The data have not been received.

1 The data exchange is in progress.

2 The data exchange is successful.

3 The data exchange fails.

CR#117, 118: Modbus TCP Destination IP

Explanations:

Setting up the destination IP address in Modbus TCP mode. See explanations on CR#70 and

#71 for how to set.

CR#119: Modbus TCP Data Length

Explanations:

Setting up the length of communication data in Modbus TCP mode. Length for 8-bit mode: K1

~K100; length for 16-bit mode: K1 ~ K200.

CR#120 ~ 219: Modbus TCP Data Buffer

Explanations:

Buffer for transmitted/received data in Modbus TCP mode.

CR#251: Error Code

Explanations:

Table of error code:

Bit No. Error

b0 The network is not yet connected.

b1 Incorrect IP setting

b2

CR#13 is set as “transmitting data”, but the data exchange

is forbidden.

b3

CR#13 is set as “transmitting data”, but the data exchange

mode has not yet been enabled.

b4 NTP-Server connection fails.

b7 SMTP-Server connection fails.

b8 DHCP has not obtained the correct network parameter.

4.3 Numbering of Left-Side Extension Modules

After DVPEN01-SL is installed properly, you need to compile the PLC program to control the extension

modules. PLC offers FROM instrcution (for reading) and TO instrcution (for writing) to control the control

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

13

registers (CR) in the extension module.

Numbering of the modules: Every extension module connected to PLC MPU has a No. to allow you to know

which module is which when compiling the PLC program. The first extension module attached at the left hand

side of the PLC MPU is numbered as K100, the second as K101, the third K102, and so on.

5 Setting up Software

This section gives instructions on how to set up DVPEN01-SL by WPLSoft and explanations on each setup

page. Before you start a setup page, you have to select “Ethernet” in the communication setting. Next, you can

search by IP address or use Auto-Search. You also can open the setup page for DVPEN01-SL by RS-232.

DVPEN01-SL is set up by UDP port 20006; therefore, you have to be aware of the relevant settings of the

firewall.

5.1 Setting up Communication & Searching for Modules

1. Communication settings

Open WPLSoft in your PC and click on “Communication Setting”.

Select “Ethernet” as the transmission type.

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

14

2. Auto-search

Press “Auto-Search” (circled) to search for every DVPEN01-SL in the network and display them in

the left column.

Move the cursor to the module you would like to set up. Double click it to enter the setup page.

You will see the basic setup page as follow.

Ethernet Communication Module DVPEN01-SL

DVP-PLC Application Manual

15

3. Searching by IP address

Set the transmission type as “Ethernet” first. Next click on the “Static IP Search” icon (circled) to

search for the designated IP.

Press the “search” icon and you will open the window for entering the IP address. Enter the IP of

DVPEN01-SL you would like to search in the IP address column, or click on the IP address in the

IP list. Press “OK» to start the searching.

The DVPEN01-SL searched is displayed in the left column. Move the cursor to the module you

would like to set up. Double click it to enter the setup page.

background image

DVPEN01-SL

Ethernet Communication Module


Operation Manual

DVP-0204320-02

Как пользоваться?

Наша цель — обеспечить Вам самый быстрый доступ к руководству по эксплуатации устройства Delta Electronics Ethernet Communication Module DVPEN01-SL. Пользуясь просмотром онлайн Вы можете быстро просмотреть содержание и перейти на страницу, на которой найдете решение своей проблемы с Delta Electronics Ethernet Communication Module DVPEN01-SL.

Для Вашего удобства

Если просмотр руководства Delta Electronics Ethernet Communication Module DVPEN01-SL непосредственно на этой странице для Вас неудобен, Вы можете воспользоваться двумя возможными решениями:

  • Полноэкранный просмотр -, Чтобы удобно просматривать инструкцию (без скачивания на компьютер) Вы можете использовать режим полноэкранного просмотра. Чтобы запустить просмотр инструкции Delta Electronics Ethernet Communication Module DVPEN01-SL на полном экране, используйте кнопку Полный экран.
  • Скачивание на компьютер — Вы можете также скачать инструкцию Delta Electronics Ethernet Communication Module DVPEN01-SL на свой компьютер и сохранить ее в своем архиве. Если ты все же не хотите занимать место на своем устройстве, Вы всегда можете скачать ее из ManualsBase.

Руководство по эксплуатации Delta Electronics Ethernet Communication Module DVPEN01-SL

Печатная версия

Многие предпочитают читать документы не на экране, а в печатной версии. Опция распечатки инструкции также предусмотрена и Вы можете воспользоваться ею нажав на ссылку, находящуюся выше — Печатать инструкцию. Вам не обязательно печатать всю инструкцию Delta Electronics Ethernet Communication Module DVPEN01-SL а только некоторые страницы. Берегите бумагу.

Резюме

Ниже Вы найдете заявки которые находятся на очередных страницах инструкции для Delta Electronics Ethernet Communication Module DVPEN01-SL. Если Вы хотите быстро просмотреть содержимое страниц, которые находятся на очередных страницах инструкции, Вы воспользоваться ими.

Понравилась статья? Поделить с друзьями:

А вот и еще наши интересные статьи:

  • Wart removal ointment инструкция по применению на русском языке
  • Синонимы к осуществляющий руководство
  • Кетонал крем инструкция от чего помогает взрослым
  • Хлоргексидин для полоскания горла инструкция по применению взрослым цена аналоги
  • Должностная инструкция оператора машинного доения в сельском хозяйстве скачать

  • 0 0 голоса
    Рейтинг статьи
    Подписаться
    Уведомить о
    guest

    0 комментариев
    Старые
    Новые Популярные
    Межтекстовые Отзывы
    Посмотреть все комментарии